Details

  • In Stock Unit:
    Each

Description

HS55128--SUPER FLUSH

Neutralizes and removes acid caused by compressor burnout

Features/Benefits

  • Biodegradable
  • Easy to use
  • Cleans in a single treatment
  • Compatible with all refrigerants and refrigeration oils
  • Does not contain halogenated solvents
  • 1-gallon jug

Super Flush Internal Coil Cleaner and System Flush

 

The best internal coil cleaner and system flush available!

One treatment cleans and removes:

  • Gum
  • Soot
  • Moisture
  • Sludge
  • Grease
  • Tar
  • Particules
  • Debris
  • Organic Acids
  • Mineral Acids
  • Carbon Deposits

Safely Cleans and Chemically Stabilizes Recovery, Recycling and Reclamation Equipment

  • Biodegradable, environmentally safe, non-flammable.
  • Safe and easy to use. Will not harm system components.
  • Cleans in a single treatment, saves time and money.
  • Does not contain halogenated solvents or hazardous ingredients.
  • Safe and compatible with all refrigerants and refrigeration oils.
  • Super cleaning agent for all A/C & refrigeration mechanical parts.

Neutralizes and Removes Acid 
Caused By Compressor Burnout.

*If compressor burnout has occurred, the compressor must be replaced according to industry standards and/or equipment manufacturer instructions. Be sure to replace filters/dryers and capillary tubes to avoid any residual contamination.

Directions: Internal coil cleaning (Condenser & Evaporator Coils)

  1. Recover and save refrigerant according to EPA requirements.
  2. Disconnect the compressor, dryer, expansion valve, accumulator, receiver, capillary tube and solenoid valves.
  3. Clean the evaporator and condenser coils separately by filling coil completely with Super Flush. Use approximately one (1) gallon of Super Flush for each ton of system capacity.
    • Small Systems: Use a container and hand operated pump to circulate Super Flush through the coils for a minimum of twenty (20) minutes.
    • Large Systems: Use a circulating pump, flexible tubing and a large container to create a closed loop system and circulate Super Flush through the coils for at least twenty (20) minutes.
  4. Collect the used Super Flush and dispose of in compliance with federal, state and local regulations and guidelines.
  5. Use pressurized dry nitrogen (100psi) to blow out coils.
  6. Clean and/or replace the expansion valve, capillary tube, solenoid valve, accumulator, and receiver. Additional system tubing should be cleaned separately.
  7. Reassemble and reconnect the systems compressor. Replace dryer and evacuate system to at least 300 microns.
  8. Recharge the system and make adjustments necessary to meet operating specifications.

Directions: System Flush (Cleaning Complete System)

  1. Recover all refrigerant form the system according the the EPA and/or system guidelines and drain excess oil.
  2. Disconnect the compressor, dryer, accumulator, receiver, expansion valve or capillary tube from the system.
  3. Connect flexible tubing to bypass compressor, dryer, accumulator, receiver, expansion valve or capillary tube creating a closed loop.
  4. Measure the correct amount of Super Flush, approximately one (1) gallon per ton of system capacity, and place in an open container large enough to accommodate the necessary volume of Super Flush. * The amount of Super Flush must be recorded to insure recovery after cleaning.*
  5. Connect a section of flexible tubing from the open container to the intake side of a circulating pump and a second section of tubing from the outlet side of the pump to the low side of the evaporator coil. Connect a third section of tubing to the high side of the condenser coil to the open container of Super Flush. This completes a circulation loop.
  6. Activate the pump to circulate Super Flush through the system for twenty (20) or thirty (30) minutes.
  7. Remove the tubing from the circulating pump and use pressurized dry nitrogen (100 psi) to blow any remaining Super Flush into the open container.
  8. Collect the Super Flush and measure the amount that was returned to the open container. Compare the amount to that originally placed in the system. Do not leave more than five (5) percent of Super Flush in the system. *Super Flush will not harm the system. However, leaving more than five (5) percent of Super Flush in the system may over fill the system's capacity and risk excess pumping pressure on the system.*
  9. Test the system for any oil, acid, or contaminants. Dispose of used Super Flush according to federal, state and local regulations.
  10. Clean out accumulator, receiver, and expansion valve separately with Super Flush.
  11. Reassemble the system- reconnect all remaining parts and connect compressor.
  12. Using a vacuum pump and micron gauge, evacuate the system to a minimum of 300 microns - recharge the system with refrigerant and oil according to equipment specifications. Start the equipment and make any necessary adjustments.

Directions: Compressor Cleanout

  1. Burnout conditions: if compressor burnout has occurred, the compressor must be replaced.
  2. Retrofitting: (a) Using a siphon pump, remove all the oil from the compressor's crankcase. (b) Place an equivalent amount of Super Flush into crankcase. (c) Leave Super Flush in crankcase fro twenty (20) minutes (agitate or stir if possible). (d) Using a siphon pump, remove the used Super Flush from crankcase and dispose of according to federal, state and local regulations. (e) Refill crankcase with oil according to equipment guidelines.

Super Flush is safe and compatible as a flush and/or cleaning agent for use in automotive and other mobile air conditioning & refrigeration systems. super flush is designed for use with closed loop flushing machines and pressurized flush guns.